MAINS CHARACTERISTICS
Nominal rated voltage range 220 V – 240 V, 50 – 60 Hz
Rated emergency voltage range* 196 V – 250 V, 0 Hz
AC voltage range 198 VAC – 264 VAC
Withstands max. 320 VAC (max. 1 hour)
DC voltage range* 176 VDC – 275 VDC
Mains current at full load 0.33 – 0.44 A
Frequency 50 Hz – 60 Hz
THD at full power < 10 %
Leakage current to earth < 0.7 mA
Tested surge protection 4 kV L/N-GND**
4 kV L-N (IEC 61000-4-5)
Tested fast transient protection 2 kV (IEC 61000-4-4)
*For emergency use, see details on page 4
**Up to 2 kV according to IEC61000-4-5, up to 4 kV L-GND or N-GND positive surge pulses.